Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* THE PROPER BACKFLOW PREVENTION DEVICE HAS BEEN INSTALLED. |
|
| 07/28/2006 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* - OK TO COVER WATER PIPING - YOU HAVE SOLENOID VALVES IN THE GROUND DIRECTLY BELOW YOUR BACKFLOW PROTECTION DEVICE FOR THE IRRIGATION SUPPLY. - AN AAV CANNOT HAVE DOWNSTREAM VALVES. - A PVB IS REQUIRED WHEN VALVES ARE LOCATED DOWNSTREAM. PVB REQUIRES CERTIFICATION. - FINAL APPROVAL WILL BE GIVEN WHEN THE PROPER DEVICE IS INSTALLED. |
|
| 07/27/2006 | PLUMBING - FINAL | Cancelled | CANCELLED PER CHARITY OF SPARTAN PLUMBING #886-4159 | |
| 07/26/2006 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* - MOST PEX MANUFACTURERS DO ALLOW THE USE OF ADHESIVE TAPE. - USE ZIP TIES TO SECURE TRACER WIRE OR PROVIDE LITERATURE ALLOWING 10 MIL. TAPE. - OFFICE BATH PIPING DROPS COULD USE TO BE SECURED OR INSULATED TO PREVENT NOISE. - 1/2" COPPER INSTALLED OUTSIDE SHALL BE INSULATED TO PROTECT FROM FREEZING. - REMOVE SHARP EDGES FROM UNISTRUT. - AN IRRIGATION & SUPPLY OUTLET HAS BEEN INSTALLED AT IRRIGATION CONTROL VALVE LOCATION. A BACKFLOW PREVENTION DEVICE IS REQUIRED FOR IRRIGATION PIPING. |
|
| 07/25/2006 | PLUMBING - FINAL | Cancelled | 1:20 PM NOT READY PER PLUMBER |