Permit: T06PL01287

Parcel: 112031630


Addresses:

3328 N STEWART AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/02/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
THE PROPER BACKFLOW PREVENTION DEVICE HAS BEEN INSTALLED.
07/28/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
- OK TO COVER WATER PIPING
- YOU HAVE SOLENOID VALVES IN THE GROUND DIRECTLY BELOW YOUR BACKFLOW PROTECTION DEVICE FOR THE IRRIGATION SUPPLY.
- AN AAV CANNOT HAVE DOWNSTREAM VALVES.
- A PVB IS REQUIRED WHEN VALVES ARE LOCATED DOWNSTREAM. PVB REQUIRES CERTIFICATION.
- FINAL APPROVAL WILL BE GIVEN WHEN THE PROPER DEVICE IS INSTALLED.
07/27/2006 PLUMBING - FINAL Cancelled CANCELLED PER CHARITY OF SPARTAN PLUMBING #886-4159
07/26/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
- MOST PEX MANUFACTURERS DO ALLOW THE USE OF ADHESIVE TAPE.
- USE ZIP TIES TO SECURE TRACER WIRE OR PROVIDE LITERATURE ALLOWING 10 MIL. TAPE.
- OFFICE BATH PIPING DROPS COULD USE TO BE SECURED OR INSULATED TO PREVENT NOISE.
- 1/2" COPPER INSTALLED OUTSIDE SHALL BE INSULATED TO PROTECT FROM FREEZING.
- REMOVE SHARP EDGES FROM UNISTRUT.
- AN IRRIGATION & SUPPLY OUTLET HAS BEEN INSTALLED AT IRRIGATION CONTROL VALVE LOCATION. A BACKFLOW PREVENTION DEVICE IS REQUIRED FOR IRRIGATION PIPING.
07/25/2006 PLUMBING - FINAL Cancelled 1:20 PM NOT READY PER PLUMBER