Permit: T06PL01283

Parcel: 10605107A

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
08/25/2006 PLUMBING - GAS PRESSURE TEST Approved
08/02/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
PRESSURE TEST ON REAR (EAST) HOUSE IS OK.
PIPE REPAIR IS OK
ONCE YOUR METER IS LOCKED OUT, IT BECOMES NECESSARY TO BRING YOUR ENTIRE GAS SYSTEM UP TO CODE.
YOU HAVE A FAIRLY NEW WATER HEATER WHICH HAS NOT BEEN INSTALLED PER CODE.
WH SHALL REST ON A LEVEL CONCRETE BASE NOT LESS THAN 3 1/2" ABOVE DIRT. T&P SHALL TERMINATE 6" - 24" ABOVE GRADE.
DOUBLE WALL B VENT REQUIRED OUTSIDE OF ENCLOSURE
COPPER PIPING SHALL BE SUPPORTED AND SHALL NOT TOUCH METAL.
PROVIDE SEDIMENT TRAPS AND AN UPPER COMBUSTION AIR OPENING.
PROVIDE ELECTRICAL BONDING SUPPORT PIPING ON ROOF
PROVIDE ROOF PENETRATION FLASHING
07/25/2006 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
CAREFULLY RE-READ THE NOTE FROM 7/24/06 AND COMPLY
CONTINUED "NOT READY" MAY RESULT IN A REINSPECTION FEE
07/24/2006 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
YOU HAVE AN ADDRESSING PROBLEM PERMIT IS FOR UNIT ONE TEST IS ON UNIT TWO
EXPOSE ALL FITTINGS THAT HAVE BEEN REPAIRED OR REPLACED -- CORRECT THE ADDRESS BEFORE YOU RECALL INSPECTION.