Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2006 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* PRESSURE TEST FROM METER OVERHEAD TO STOVE/COOKTOP, WALL HEATER, WATER HEATER & FURNACE OK GAS CARD AT METER S.W GAS 889-1888 |
|
| 08/09/2006 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1. NO PIPING SHALL BE UNDERGROUND UNDER BUILDING OR STRUCTURE 2. PROVIDE 10 PSI TEST WITH NO LEAKAGE FOR 10 MINUTES 3. PROVIDE AGA OR CSA APPROVED GAS VALVES AT ALL APPLIANCES. 4. PIPING TO BE SUPPORTED AT CHANGES OF DIRECTION & AT 8' INTERVALS MINIMUM 3" ABOVE ROOF. 5. WATER HEATER VENT TO BE MADE UP CORRECTLY AND HAVE 3-GALV SCREWS AT EACH JOINT. 6. WATER HEATER TEMPERATURE & PRESSURE RELIEF TO GRAVITY DRAIN TO DAYLIGHT OR PROVIDE SIGNED BY CITY PETITION OF APPEAL FORM FOR ALTERNATE FORM OF TEMPERATURE & PRESSURE RELIEF WITH CORRECT INSTALLATION. 7. PROVIDE BONDING OF BUILDING GAS PIPING. |