Permit: T06PL01232

Parcel: 133251200


Addresses:

8525 E 3RD ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
07/13/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
15 PSI TEST FROM METER OVERHEAD TO ROOFTOP UNIT AND WATER HEATER OK
GAS CARD AT METER S.W. GAS 889-1888
07/12/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. TEST SHALL HOLD WITH NO PRESSURE LOSS.
2. PIPING TO WATER HEATER TO BE CONFIGURED TO PROVIDE PULL SPACE FOR WATER HEATER.
3. REMOVE TAPE AT SINGLE TO DOUBLE WALL VENT CONNECTION AT WATER HEATER & PROVIDE 3-GALV SCREWS AT EACH JOINT OF WATER HEATER VENT PIPING.
4. WATER HEATER VENT TO TERMINATE MINIMUM 2' ABOVE COMBUSTION AIR INTAKE.