Permit: T06PL01230

Parcel: 136081420


Addresses:

2021 S HARRISON RD

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
07/17/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
07/14/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE CORRECT DOUBLE WALL FOR FURNACE VENT EXTENSION ABOVE COOLER INTAKE.
2. PROVIDE #4 OR #6 BENDING WIRE
07/12/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE RIGID NIPPLE THRU FURNACE APPLIANCE HOUSING
2. PROVIDE SEDIMENT TRAPS AT GAS INLETS TO WATER HEATER & FURNACE.
3. PROVIDE BONDING OF BUILDING GAS PIPING.
4. GRAVITY DRAIN TO DAYLIGHT FOR TEMPERATURE & PRESSURE RELIEF OF WATER HEATER WITH RIGID APPROVED PIPING TERMINATING WITH 90 DEGREES DOWN.
5. PROVIDE 3-GALV SCREWS AT EACH JOINT OF VENT PIPING FOR WATER HEATER, VENT TO TRAVEL IN UPWARD DIRECTION MINIMUM 1/4" PER FOOT.
6. VENT FROM FURNACE WHEN WITHIN 10' OF COOLER INTAKE TO BE 2' ABOVE TOP OF COOLER WITH APPROVED DOUBLE WALL VENT PIPING.