Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 07/14/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE CORRECT DOUBLE WALL FOR FURNACE VENT EXTENSION ABOVE COOLER INTAKE. 2. PROVIDE #4 OR #6 BENDING WIRE |
|
| 07/12/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE RIGID NIPPLE THRU FURNACE APPLIANCE HOUSING 2. PROVIDE SEDIMENT TRAPS AT GAS INLETS TO WATER HEATER & FURNACE. 3. PROVIDE BONDING OF BUILDING GAS PIPING. 4. GRAVITY DRAIN TO DAYLIGHT FOR TEMPERATURE & PRESSURE RELIEF OF WATER HEATER WITH RIGID APPROVED PIPING TERMINATING WITH 90 DEGREES DOWN. 5. PROVIDE 3-GALV SCREWS AT EACH JOINT OF VENT PIPING FOR WATER HEATER, VENT TO TRAVEL IN UPWARD DIRECTION MINIMUM 1/4" PER FOOT. 6. VENT FROM FURNACE WHEN WITHIN 10' OF COOLER INTAKE TO BE 2' ABOVE TOP OF COOLER WITH APPROVED DOUBLE WALL VENT PIPING. |