Permit: T06PL01140

Parcel: 110140170

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06PL01140

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/12/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
14 PSI TEST (REPAIR AT BUILDING RISER) FROM METER THRU EXISTING TO DRYER, WATER HEATER, ROOFTOP UNIT OK
GAS CARD AT METER SW GAS 889-1888
GAS CARD AT METER
SW GAS 889-1888
07/05/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- 127 IS LOCATED BEHIND POOL
- GAUGE READING 0
- CHECK FOR LEAKS
- PROVIDE PRESSURE TEST USING A GAUGE WITH 1/10 PSI INCREMENTATIONS.
- AGA VALVES REQUIRED AT APPLIANCES
- REMOVE OLD GAS COCK ON ROOF
- SECURE GAS PIPNG AT DRYER
- A RELATIVELY NEW WATER HEATER IS INSTALLED.
- PROVIDE A PERMIT FOR WH INSTALLATION.
- PROVIDE A PAN UNDER WH
- SECURE VENT CONNECTOR W/GALV SHEET METAL SCREWS
- T&P RELIEF DRAIN SHALL BE HARD PIPED WITHOUT FLEX.
- PROVIDE BONDING OF GAS LINE.
- SUPPORT GAS PIPING ON ROOF.