Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 08/28/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - ADD WH REPLACEMENT AND RELOCATION TO PERMIT. - SECURE PIPING AT WH. PROVIDE SEDIMENT TRAP AT WH & FURNACES - HARD PIPE T&P. REMOVE TAPE FROM VENT CONNECTOR TO VENT TRANSITION. - TERMINATE T&P 6"-24" ABOVE GROUND. - WATER HEATER ON WOOD PLATFORM REQUIRES A DRAIN PAN - 3/4" PIPING SUPPLING 100,000 BTU FURNACE AND 65000 BTU STOVE IS UNDERSIZED. PROVIDE 1" TO BRANCH CONNECTION FOR STOVE. - 1/2" PIPING TO 100,000 BTU FURNACE AT 70' IS UNDERSIZED, PROVIDE 3/4 TO POINT OF CONNECTION. - PROVIDE ROOF FLASHING AT 1 1/4" ROOF PENETRATION. - WH FLUE VENT IS TO BE RAISED TO 1' ABOVE VERTICAL SIDE WALL. - PROVIDE ACCESS TO INSPECT WATER PIPING TO NEW WH LOCATION. |