Permit: T06PL01089

Parcel: 136072480


Addresses:

9430 E PALM TREE DR

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
07/05/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
15 PSI TEST FROM METER OVERHEAD TO WATER HEATER/FURNACE OK
07/03/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
SHALL HOLD FOR THIME DURATION WITH NO PRESSURE LOSS
06/29/2006 PLUMBING - GAS PRESSURE TEST Cancelled CANCELLED PER STEPHANIE OF PROFESSIONAL PLUMBING #622-0122
06/29/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TEST SHALL BE IN PLACE AND HOLDING WITH NO PRESSURE LOSS
2) VENTS FROM WATER HEATER/FURNACE SHALL BE 2' ABOVE COMBUSTION AIR INTAKE WITH DBL WALL VENT PIPE AND CAP
3) BONDING SHALL BE TO COLD WATER PIPING
4) PROVIDE CITY SIGNED PETITION OF APPEAL FOR ALTERNATE FORM OF T & P RELEASE ON SITE. PROVIDE 125 POUND PRESSURE RELIEF AT EXTERIOR HOSE BIB AND PROVIDE VACUUM BREAKER AT NEW HOSE BIB AT THIS LOCATION