Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/28/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) GAS CARD SHALL BE ISSUED BY MECH INSPECTOR |
|
| 06/26/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NOTE: A DRIP LEG IS NOT A SEDIMENT TRAP 2) PROVIDE SEDIMENT TRAPS AT WATER HEATER 3) T & P DRAIN TO BE 1" ABOVE TOP LIP OF PAN 4) PROVIDE PROOF OF NEW A/C FURNACE PERMIT AND INSPECTION APPROVAL TO RECEIVE GAS CARD 5) PROVIDE MINIMUM 1" CLEARANCE FROM COMBUSTIBLES FOR DBL WALL VENT AT WATER HEATER. PETITION OF APPEAL #2001.118 ON SITE 6) BREAK OFF TAMPER SCREW ON NEW VACUUM BREAKER |