Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T06PL01038

Parcel: 134100770


Addresses:

8002 E TIMROD ST


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T06PL01038

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
06/26/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
1) 20 PSI TEST FROM METER OVERHEAD TO WATER HEATER/FURNACE OK
06/22/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEDIMENT TRAPS ARE REQUIRED ON WATER HEATER & FURNACE AT GAS INLET.
2. DRIP LUG CANNOT BE SUPPORT FOR GAS PIPING. IT SHALL BE SECURED PROPERLY IN WATER HEATER/FURNACE CLOSET.
3. WATER HEATER TEMPERATURE & PRESSURE RELIEF DRAIN SHALL BE FULL SIZE APPROVED MATERIAL GRAVITY DRAIN TO DAYLIGHT.
4. REMOVE TAPE FROM SINGLE TO DOUBLE WALL DRAFT SPACE ON VENT CONNECTOR FROM WATER HEATER/FURNACE
5. PROVIDE BONDING OF BUILDING GAS PIPING.
6. VENT FROM WATER HEATER/FURNACE SHALL BE 2' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF INTAKE WITH DOUBLE WALL VENT & CAP.