Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T06PL01038
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/26/2006 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* 1) 20 PSI TEST FROM METER OVERHEAD TO WATER HEATER/FURNACE OK |
|
| 06/22/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEDIMENT TRAPS ARE REQUIRED ON WATER HEATER & FURNACE AT GAS INLET. 2. DRIP LUG CANNOT BE SUPPORT FOR GAS PIPING. IT SHALL BE SECURED PROPERLY IN WATER HEATER/FURNACE CLOSET. 3. WATER HEATER TEMPERATURE & PRESSURE RELIEF DRAIN SHALL BE FULL SIZE APPROVED MATERIAL GRAVITY DRAIN TO DAYLIGHT. 4. REMOVE TAPE FROM SINGLE TO DOUBLE WALL DRAFT SPACE ON VENT CONNECTOR FROM WATER HEATER/FURNACE 5. PROVIDE BONDING OF BUILDING GAS PIPING. 6. VENT FROM WATER HEATER/FURNACE SHALL BE 2' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF INTAKE WITH DOUBLE WALL VENT & CAP. |