Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 15 PSI TEST IS OK CORRECTIONS HAVE BEEN MADE LEFT GAS CARD. |
|
| 06/22/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ADD RELOCATION AND REPLACEMENT OF WH TO PERMIT. 2. PROVIDE ACCESS TO ATTIC FOR INSPECTION. 3. PROVIDE BONDING OF GAS LINE. 4. PROVIDE DOUBLE WALL VENT PIPING OUTSIDE OF ENCLOSURE. 5. SUPPORT VENT W/PIPE SUPPORTS. 6. INSTALL INSULATION IN ACCORDANCE W/MANUFACTURERS SPECS, SEAL JOINTS. |