Permit: T06PL00998

Parcel: 135022120

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/30/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
07/03/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PROVIDE BONDING OF BUILPIPING GAS PIPING AS REQUESTED ON PAST INSPECTIONS
GAS CARD AT MOTOR 889-1888
06/28/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHALL PROVIDE ITEMS #2, 3, 4, 5, 6 & 8 FROM 6/23/06
2) PROVIDE NIPPLE THRU APPLIANCE HOUSING AT WEST FURNACE
3) CAP OLD GAS PIPING
06/23/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PIPING SYSTEM CANNOT HAVE APPLIANCE FLEX EXCEPT AT APPLIANCES. PROVIDE RIGID PIPE.
2. PROVIDE 3-GALV SCREWS AT EACH JOINT OF VENTS FROM APPLIANCES AND REMOVE TAPE AT SINGLE TO DOUBLE WALL CONNECTION OF FURNACE.
3. WATER HEATER REQUIRES TEMPERATURE & PRESSURE RELIEF DRAIN TO GRAVITY DRAIN TO DAYLIGHT OR PROVIDE PETITION OF APPEAL FORM SIGNED BY CITY FOR ALTERNATE FORM OF TEMPERATURE & PRESSURE RELIEF ON SITE WITH CORRECT INSTALLATION.
4. SINGLE WALL VENT REQUIRES 6" MINIMUM CLEARANCE FROM COMBUSTIBLES DOUBLE WALL VENT REQUIRES 1" MINIMUM CLEARANCE FROM COMBUSTIBLES.
5. PROVIDE SEDIMENT TRAPS AT GAS INLET FOR WATER HEATER & FURNACES.
6. PROVIDE BONDING OF BUILDING GAS PIPING.
7. SECURE ALL INTERIOR GAS PIPING.
8. VENT FROM WEST FURNACE TO BE 2' ABOVE TOP OF COMBUSTION AIR INTAKE WITH DOUBLE WALL VENT PIPE INSTALLED CORRECTLY WITH APPROVED VENT CAP WHEN WITHIN 10' OF INTAKE.
9. PROVIDE FIRM BEDDING FOR EXTERIOR GAS PIPING.