Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
06/22/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
06/20/2006 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1. VERTICAL PIPE AT METER TO BE SUPPORTED.
2. ALL ROOF TOP GAS TO BE SUPPORTED.
3. PIPING PASSING THROUGH THE ROOF TO HAVE APPROVAL FLASHING.
4. PROVIDE ACCESS TO ROOF.
5. WHEN TESTING WITH LESS THAN TEN POUNDS, A GAUGE MEASURING NO MORE THAN FIFTEEN POUNDS IN 1/10 POUND INCREMENTATION IS REQUIRED -- YOUR GAUGE REQUIRES A MINIMUM TEN POUND TEST.
06/16/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
15 PSI TEST IS OK
SECURE GAS PIPE @ WATER HEATER.
PROVIDE MIN. 3 SCREWS IN ALL JOINTS OF VENT CONNECTORS
PROVIDE ELECTRICAL BOND TO GAS PIPING
PROVIDE HIGH & LOW COMBUSTION AIR VENTS TO BOTH WATER HEATER ROOMS.
PROVIDE A NEW T&P RELIEF VALVE ON OLD WATER HEATER.
REPLACE BROKEN ELBOW AT END OF T&P DRAIN.
BE SURE ALL ACTIVITIES ON THIS PERMIT ARE CALLED IN FOR INSPECTION.