Permit: T06PL00927


Addresses:

10500 E DREXEL RD


Inspection Status: Approved

Inspection History: SITE - SEWER

Permit Number - T06PL00927

Inspection Description - SITE - SEWER

Inspection Status - Approved

Date Description Inspector Results Comments
12/20/2007 SITE - SEWER Approved IVRS - Inspection :*
06/28/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
FROM MANHOLE #23 TO CLEANOUT #14
LOTS 783-788 AIR TEST OK
FROM MANHOLE #24 TO CLEANOUT #12
LOTS 799-794 AIR TEST OK
FROM MANHOLE #25 TO CLEANOUT #10
LOTS 777-783 AIR TEST OK
FROM MANHOLE #26 TO CLEANOUT #8
LOTS 795-800 AIR TEST OK
FROM MANHOLE #27 TO CLEANOUT #6
LOTS 771-776 AIR TEST OK
FROM MANHOLE #28 TO CLEANOUT #4
LOTS 801-804 AIR TEST NOT READY
FROM MANHOLE #29 TO CLEANOUT #2
LOTS 765-770 AIR TEST NOT READY

NOTES FROM 6/21/07 BELONG TO PERMIT #T06PL00926
PHASE II
06/21/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
FROM MANHOLE #4 TO C.O. #4 AIR TEST LOTS 491-196 OK
FROM MANHOLE #4 TO C.O. #1 AIR TEST LOTS 485-490 OK
FROM MANHOLE #5 TO C.O. #8 AIR TEST LOTS 497-500 OK
FROM MANHOLE #5 TO C.O. #5 AIR TEST LOTS 479-484 OK
FROM MANHOLE #6 TO C.O. #12 AIR TEST LOTS 500-505 OK
FROM MANHOLE #6 TO C.O. #9 AIR TEST LOTS 473-478 OK
05/09/2007 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
MEETING WITH BERT PULTE CONST. ABOUT TERMINATION OF INLINE 6" CLEANOUTS ON SEWERS TO BE TO GRADE WITH TRAFFIC RATED COVERS & CORRECT TERMINATION OF CLEANOUTS.
05/04/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
6" BEDDING, LAYING, TRACER, SHADING 767 THRU 806 WITH HCS LATERALS EXCEPT FOR LOTS 765 & 766 WHICH SHALL REQUIRE 4" PIPING INSTALLED INTO MAIN FITTINGS AT LATER DATE PRIOR TO TESTING DUE TO CONST. TRAILER IN WAY.
05/01/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
6" BEDDING, LAYING, TRACER, SHADING FOR LOTS 777 THRU 800 INCLUDING HCS LATERALS OK
SHALL PROVIDE VERIFICATION OF GRADE, AIR TESTING AT LATER DATE CLEANOUTS TO BE TO GRADE FOR FINAL.