Permit: T06PL00918

Parcel: 134081040

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/07/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
15 PSI NEW PIPING OVERHEAD TO FURNACE/WATER HEATER ONLY OK
GAS CARD AT METER S.W GAS 889-1888
PETITION OF APPEAL #2006.096 ON SITE.
06/06/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WATER HEATER DRAFT HOOD & VENT TO BE MADE UP CORRECTLY WITH 3-GALV SCREWS AT EACH JOINT OF VENT PIPING FOR BOTH FURNACE & WATER HEATER.
2. REMOVE TAPE AT SINGLE TO DOUBLE WALL VENT CONNECTION ON BOTH WATER HEATER & FURNACE.
3. INSTALL WATER HEATER T&P DRAIN PROPERLY.
4. SECURE GAS PIPING IN WATER HEATER/FURNACE CLOSET PROPERLY.
5. VENTS FROM WATER HEATER/FURANCE TO BE MINIMUM 2' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF INTAKE WITH DOUBLE WALL VENT TO TERMINATION AT APPROVED VENT CAP.
6. PROVIDE BONDING OF BUILDING GAS PIPING.
7. PROVIDE NIPPLE WITH NO THREADS ON DISCHARGE END AT 125# PRESSURE RELIEF DEVICE.
PETITION OF APPEAL #2006.096 ON SITE.