Permit: T06PL00857

Parcel: 127041540


Addresses:

4914 E ROSEWOOD ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
06/02/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
06/01/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
15 PSI TEST IS O.K ON PLASTIC PIPE ONLY.
PROVIDE APPROVED TAPE PRIMER ON ALL BURIED JOINTS PRIOR TO TAPE.
PRESSURE TEST MUST BE ON ALL GAS PIPING.
VENT ON WATER HEATER OUTDOORS MUST BE DOUBLE WALL PIPE. PROVIDE 1" CLEARANCE FROM COMBUSTIBLES OR INSTALL NEW TANKLESS WATER HEATER. PROVIDE ENCLOSURE AROUND WATER HEATER.
REMOVE 1/4" ID FLEX FROM CLOTHES DRYER. USE AN APPROVED SHUT OFF VALVE.
OK TO BACKFILL PLASTIC PIPE ONLY.