Permit: T06PL00841

Parcel: 121121140


Addresses:

5249 E BELLEVUE ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/17/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
11/14/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
NO ANSWER AT DOOR 4PM

I WILL COME BY MONDAY
HAVE BOTH PERMIT CARDS AVAILABLE
DON'T FORGET THE 1" CLEARANCE REQUIRED
BETWEEN B-VENT AND WOOD AT ROOF PENETRATION
11/03/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROPERLY SOLVENT CEMENT CPVC AND SUPPORT EVERY 36"
TERMINATE W/OUT TRAP AND AS PREVIOUSLY NOTED
PROVIDE A FULL SIZED VALVE AT WATER SUPPLY

5" TYPE B VENT REQUIRED THRU ROOF AND TO TERMINATION POINT 3' ABOVE COOLER, SECURE EACH CONN. OF VENT CONNECTOR W/3 SCREWS
09/12/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- T&P SHALL GRAVITY DRAIN TO EXTERIOR AND TERMINATE 6"-24" ABOVE GROUND WITHOUT THREADS. USE CPVC, GALVANIZED OR COPPER RIGID TUBING.
- REMOVE BLACK IRON 90 ON HW
- PROVIDE SEDIMENT TRAP AT GAS CONNECTION
- CORRECT VENTING, USE GALVANIZED VENT PIPE, SECURE WITH GALVANIZED SHEET METAL SCREWS.