Permit: T06PL00812

Parcel: 122060480


Addresses:

4345 E PIMA ST


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T06PL00812

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
06/19/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
06/14/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
LEAKING
05/23/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1. PROVIDE SUPPORTS AT CHANGES OF DIRECTION AND AT 6' INTERVALS AND SECURE PIPING TO SUPPORTS. ALL UNITS.
4345 -- PROVIDE NIPPLE THRU APPLIANCE HOUSING AND HAVE FLEX ON SITE.
4347 - 14.5 OK
4349 - 14.8-9 OK
4351 - 13.6 DENIED
4359 - 14.6-7 DENIED
4361 - 4397 PRESSURE TEST OK
GAS CARD ON SITE.
ALL OTHER ADDRESS REPAIR REPIPE, RETEST.
ALL REPIPES SHALL BE BROUGHT UP TO 2003 UPC REQUIREMENTS
NOTE: UNITS ON ROOF HAVE ELECTRICAL ISSUES
EXPOSED WIRING, DISCONNECT BOXES LAYING ON ROOF ETC.
THIS ISSUE SHOULD BE PERMITTED AND REPAIRED.
05/19/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
SHALL HAVE PRESSURE TEST ON ALL ADDRESSES AT TIME OF INSPECTION. NEW PIPING OR ALTERED PIPING IS NOT A GAS RECONNECT. ACCESS SHALL BE REQUIRED TO ALL UNITS ON DAY OF RE-INSPECTION. ACCESS TO ALL ENTIRE GAS SYSTEMS SHALL ALSO BE REQUIRED. PLEASE HAVE AN ADULT PRESENT TO PROVIDE ACCESS TO ALL UNITS TO BE INSPECTED. FEES ARE PAID ON (14) UNITS.