Permit: T06PL00797

Parcel: 11621192C

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
05/19/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
10.5 PSI
PET. OF APPEAL #2006-077
05/16/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
3.7 PSI 4:04 P.M
PRESSURE DROP IS MOST LIKELY CAUSED BY THE OLD GAS VALVE BEHIND W.H
1. OBTAIN PERMIT FOR NEW WATER HEATER AND NEW FURNACE. IF YOU ARE UNABLE TO RUN TEMPERATURE AND PRESSURE RELIEF VALVE TO OUTSIDE WITHOUT TRAPPING LINE YOU WILL NEED TO OBTAIN A CODE VARIANCE AND INSTALL WH ACCORDINGLY.
2. REMOVE OLD GAS VALVE.
3. SECURE VENT TO CONNECTOR WITH SCREWS.
4. RETEST GAS PIPING.