Permit: T06PL00747

Parcel: 133262050


Addresses:

401 N SARNOFF DR

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/24/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
11 PSI TEST NEW PIPING UNDERGROUND UP AT BUILDING ABOVE GRADE TO EXISTING THRU TO WATER HEATER, FURNACE, DRYER OK
GAS CARD AT METER.
05/23/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
10:55 NO MESSAGE #
NO ACCESS PLEASE HAVE AN ADULT PRESENT AT REINSPECTION.
05/18/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. TEST GAS PIPING IN ITS ENTIRETY.
2. SECURE & SUPPORT GAS PIPING AT BUILDING EXTERIOR.
3. PROVIDE AGA OR CSA APPROVED GAS VALVES AT ALL APPLIANCES.
4. PROVIDE CORRECT VENT CONNECTION FOR WATER HEATER DRAFT HOOD TO DOUBLE WALL VENT.
5. VENT FROM WATER HEATER & FURNACE WHEN WITHIN 10' OF COOLER INTAKE TO BE 3' ABOVE FOR WATER HEATER
2' ABOVE FOR FURNACE TOP OF COOLER INTAKE WITH DOUBLE WALL VENT PIPING & CAP.
PROVIDE 3-GALV SCREWS AT EACH JOINT OF FLUE VENT PIPING.
6. PROVIDE BONDING OF BUILDING GAS PIPING.
05/16/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PLEASE SCHEDULE AN INSPECTION WHEN AN ADULT WILL BE PRESENT.