Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 06/15/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 36" X 1/4" ID APPLIANCE CONNECTOR APPEARS TO HAVE BEEN REUSED AND APPEARS TO BE UNDERSIZED. 1. REPLACE APPLIANCE CONNECTOR W/PROPERLY SIZED NEW CONNECTOR. 2. ONE JOINT ON VENT CONNECTOR IS NOT PROPERLY MADE, ALSO SECURE VENT CONNECTOR WITH 3 SCREWS AT EACH JOINT. TWO SCREWS DIRECTLY NEXT TO EACH OTHER DOES NOT PREVENT MOVEMENT IN EACH DIRECTION. 3. PROVIDE 1" OF CLEARANCE BETWEEN VENT AND WOOD CEILING. 4. WATER HEATER SUPPLY VALVE IS REQUIRED TO BE A FULL PORT VALVE. 5. EXTEND WATER HEATER VENT TO 3 FEET ABOVE SWAMP COOLER W/TYPE B VENT AND CAP. |