Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06PL00682
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/16/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* SEAL CLEANOUT PLUGS. |
|
| 05/22/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* MAKE CONNECTION AT HOUSE. BREAK SEPTIC TANK BACKFILL |
|
| 05/12/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* CALLED AT 9:11 A.M 955-0098 ARRIVED 9:49 PCWM PERMIT NOT NEEDED IF SADDLE IS USED. TIE IN TO PUBLIC SEWER ABOVE FLOW LINE. THERE IS NOT AN ELEVATION PLAN. SEWER IS INSTALLED AT 1/4-3/8" PER FOOT SLOPE. PROVIDE UNIFORM SLOPE OF 1/8" PER FOOT. IT APPEARS THAT ADEQUATE FALL EXISTS. AFTER CONNECTING TO PUBLIC SEWER INSTALL A TEST WYE AS CLOSE AS POSSIBLE AND TESTES PRIVATE SEWER 2" BUILDING SEWER ON EAST SIDE OF HOUSE REQUIRES A CLEANOUT. EXPOSED PIPNIG ON WALL SHALL BE METAL PIPE. GALVANIZED PIPING IS NOT TO BE USED WITHIN 6" ON GROUND PROVIDE FLASHING. EXPOSE CONNECTION TO BUILDING DRAIN ON EAST SIDE. |