Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 06/06/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* P OF A 2006.062 - OK DRAIN PAN PLUG IS OK COMPLETE THE REMAINING REQUIRED CORRECTIONS. |
|
| 05/12/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PETITION OF APPEAL IS NECESSARY BECAUSE T&P TERMINATION IS BELOW GRADE. 1. PETITION OF APPEAL FOR T&P RELIEF DRAIN SHALL BE ON SIGHT FOR INSPECTION. 2. OUTLET OF DRAIN PAN SHALL BE PLUGGED. 3. OUTLET OF PRESSURE RELIEF SHALL TERMINATE WITHOUT THREADS. 4. FLUE PIPING SHALL HAVE 3 SCREWS AT EACH JOINT SCREWS SHALL PENETRATE BOTH PIPES AT JOINT. 5. GAS VALVE SHALL BE AGA RATED. 6. INTERMIXING OF DISSIMILAR METALS IS NOT NECESSARY, THEREFORE NOT ACCEPTABLE. |
|
| 05/01/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NEW GAS FIRED WATER HEATER INSTALLED. NEW T&P DRAIN LOWER THAN EXISTING - MAY NOT DUMP T&P RELIEF IN A PAN WITHOUT "PETITION OF APPEAL" BESIDES THE DRAIN IS OPEN ON THE PAN REMOVE THE TAPE BETWEEN THE VENT AND THE VENT CONNECTOR. |