Permit: T06PL00668

Parcel: 118035770


Addresses:

2709 W SHERYL PL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/08/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
06/06/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
P OF A 2006.062 - OK
DRAIN PAN PLUG IS OK
COMPLETE THE REMAINING REQUIRED CORRECTIONS.
05/12/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PETITION OF APPEAL IS NECESSARY BECAUSE T&P TERMINATION IS BELOW GRADE.
1. PETITION OF APPEAL FOR T&P RELIEF DRAIN SHALL BE ON SIGHT FOR INSPECTION.
2. OUTLET OF DRAIN PAN SHALL BE PLUGGED.
3. OUTLET OF PRESSURE RELIEF SHALL TERMINATE WITHOUT THREADS.
4. FLUE PIPING SHALL HAVE 3 SCREWS AT EACH JOINT SCREWS SHALL PENETRATE BOTH PIPES AT JOINT.
5. GAS VALVE SHALL BE AGA RATED.
6. INTERMIXING OF DISSIMILAR METALS IS NOT NECESSARY, THEREFORE NOT ACCEPTABLE.
05/01/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. NEW GAS FIRED WATER HEATER INSTALLED.
NEW T&P DRAIN LOWER THAN EXISTING -
MAY NOT DUMP T&P RELIEF IN A PAN
WITHOUT "PETITION OF APPEAL"
BESIDES THE DRAIN IS OPEN ON THE PAN
REMOVE THE TAPE BETWEEN THE VENT AND THE VENT CONNECTOR.