Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06PL00667
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/20/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
02/19/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SUPPORT 2" PIPING AT EXISTING PAINT BOOTH 2. TERMINATE ALL REGULATOR VENTS PER NOTE #5 PAGE P.1 |
|
12/21/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
07/13/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* SHALL VENT REGULATOR FROM PAINT OVEN TO EXTERIOR & WEATHERPROOF TERMINATION. PRIOR TO OPERATING THIS OVEN. |
|
10/03/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE MECHANICAL CITY APPROVED PLAN & PERMIT FOR NEW PAINT BOOTH AT NORTH END OF GAS PIPING RUN & HAVE MECHANICAL INSPECTOR LOOK AT VENTING FOR EXISTING PAINT OVEN ON WEST END OF GAS RUN. MECHANICAL INSPECTOR WILL PROVIDE GAS CLEARANCE CARD. |
|
10/02/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTES FROM 9/29/2006 INSPECTION AND COMPLY |
|
09/29/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. REPLACE THREAD PROTECTOR AT WATER HEATER. 2. WATER HEATER VENT TO BE APPROVED DOUBLE WALL THRU CEILING & ROOF WITH APPROVED VENT CAP. 3. PROVIDE UPPER COMBUSTION AIR FOR WATER HEATER. 4. PROVIDE HANGERS FOR 3/4" BRANCH OVERHEAD TO WATER HEATER. SUPPORT PIPING AT WATER HEATER. 5. SUPPORT GAS PIPING TO PRESSURE WASHER & HARD PIPE TO UNIT. 6. PROVIDE INSTALLATION INSTRUCTIONS FOR PRESSURE WASHER. NEED CORRECT VENTING FOR COMBUSTIBLES (DEVICE IS IN ENCLOSED AREA) WITH COOLER INTAKE NEAR. NEED INFORMATION ON POSSIBLE PRESSURE RELIEF. 7. PROVIDE PROOF OF INSPECTION ON NEW PAINT BOOTH AT NORTH END OF GAS SYSTEM. IT APPEARS TO BE NEW NOT EXISTING. |