Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T06PL00667
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/19/2008 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* GAS CARD AT METER CONTRACTOR TO VERIFY NO LEAKAGE DOWNSTREAM OF APPLIANCE SHUT OFF VALVES |
|
12/21/2007 | PLUMBING - GAS PRESSURE TEST | Denied | WILL BE REOPENED FOR GAS PIPING TEST, SYSTEM WILL BE RETESTED WHEN CORRECT REGULATION OF 5 PSI GAS TO CORRECT PRESSURES AT EACH APPLIANCE IS ACHEIVED AND VERIFIED. ALL REGUALTORS SHALL BE LABELED PROPERLY PER SECTION 1209.7.7 2006 UPC. ALL VENTS FROM REGULATORS TO BE FULL SIZE PIPING PROPERLY TERMINATED PER SECTION 1209.7.5 OF 2006 UPC AND NFPA 54:.8.5.1 WITH CORRECT DISTANCE FROM INTAKES AND SOURCES OF IGNITATION. ALL VENT TERMINATIONS SHALL PREVENT ON TRY OF WATER, INSECTS AND OTHER FOREIGN MATERIALS. TUCSON PLUMBING IS CONTRACTOR OF RECORD TO BE CHANGED ON THIS PERMIT ACTIVITY PLEASE PROVIDE A QUALIFIED REPRESENTATIVE TO VERIFY AND START UP ALL EQUIPMENT |
|
10/03/2006 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | 13 PSI TEST FROM METER TO WATER HEATER, PRESSURE WASHER, WEST EXISTING PAINT OVEN, NEW NORTH PAINT BOOTH APPROVED. |