Permit: T06PL00661

Parcel: 133100360


Addresses:

8501 E FAIRMOUNT PL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/27/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
PETITION OF APPEAL ON SITE #2006.065
12 PSI TEST NEW PIPING FROM METER TO EXISTING SERVICE ENTRY AND OVERHEAD TO WATER HEATER/FURNACE OK
GAS CARD AT METER - SW GAS 889-1888
04/25/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE PERMIT FOR NEW WATER HEATER.
PROVIDE PERMIT FOR NEW A/C FURNACE.
1. REMOVE COMBUSTIBLE MATERIAL FROM WATER HEATER FLUE VENT PIPING AND PROVIDE 6" MINIMUM CLEARANCE FROM SINGLE WALL VENT CONNECTOR AT WATER HEATER. FROM COMBUSTIBLES.
2. MAKE WATER HEATER VENT UP CORRECTLY.
3. PROVIDE APPROVED INSTALLATION FOR WATER HEATER TEMPERATURE & PRESSURE RELIEF DRAIN.
4. SUPPORT PIPING ALONG WALL SECURELY (PLUMBERS TAPE DOES NOT DO THIS IN A APPROVED MANNER).
5. WATER HEATER VENT TO TERMINATE MINIMUM 3' ABOVE TOP OF COOLER WHEN WITHIN 10' OF COOLER INTAKE.
6. PROVIDE BONDING OF BUILDING GAS PIPING.
7. TAPE & PRIME ALL TOOL MARKS ON PIPE UNDERGROUND. GAS CLEARANCE WILL NOT BE ISSUED WITHOUT ABOVE PERMITS & INSPECTION.