Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06PL00653
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/08/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
04/24/2006 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* PRESSURE TEST OK PIPING OK WATER HEATER T&P VALVE MUST GO TO OUTSIDE PROVIDE ELECTRICAL BONDING OF GAS LINE WH FLUE VENT - DOUBLE WALL REQUIRED IN CONCEALED LOCATIONS. |