Permit: T06PL00612

Parcel: 110073340


Addresses:

4144 E DESERT PL

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
05/03/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
05/01/2006 PLUMBING - INTERMEDIATE Denied EPOXY IS NOT AN APPROVED THREAD SEALANT. ALSO UPC REQUIRES THAT SHOWER VALVES BE ANTI-SCALD PRESSURE BALANCED. YOUR PLAN CALLS FOR FIXTURES TO BE REPLACED.
04/28/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WATER TEST WASTE & VENT THRU ROOF PER PLAN OK
WATER PIPING OK
1. PROVIDE INSULATION ON EXTERIOR TO PROTECT FROM FREEZING.
2. PROVIDE CORRECT DRYER VENT.
3. SUPPORT SHOWER VALVES.
04/18/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE CORRECT SUPPORT FOR WATER PIPING.
2. PROVIDE CORRECT DRAINAGE FOR LAV AND WASHER BOX WITH CORRECT VENTING.
3. UNIONS ON WATER PIPING CANNOT BE IN UNACCESSIBLE LOCATION.
4. WATER HEATER TO BE INSTALLED ON APPROVED PAD, IN WEATHERPROOF ENCLOSURE, CORRECTLY.
5. EXPOSE ALL PIPING.
6. PROVIDE WATER PIPING THAT IS NOT DAMAGED.
7. PROVIDE TESTING ON ALL PIPING.
8. PROVIDE CITY APPROVED PLAN FOR ADDITION OF WASHER DRAINAGE.
9. PROVIDE DIELECTRIC PROTECTION FOR SERVICE CONNECTION.