Inspection History: SITE - SEWER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2006 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* | |
| 04/25/2006 | SITE - SEWER | Partial Approval | IVRS - Inspection :* FROM #3 TO MANHOLE #1 OK AIR TEST FROM MANHOLE #3 TO MANHOLE #1 INCLUDING HCS LATERALS OK |
|
| 04/20/2006 | SITE - SEWER | Partial Approval | IVRS - Inspection :* INSTALLATION OF (5) 4" HCS LATERALS TO 2-WAY CLEANOUT OK |
|
| 04/19/2006 | SITE - SEWER | Partial Approval | IVRS - Inspection :* FROM EXISTING MANHOLE #3 WEST TO 20', 6" DUCTILE IRON TRANSITION TO 6" SDR 35 TO MANHOLE #1 (NEW) INCLUDING (5) 6X4 HCS WYES, SHADING, BEDDING, LAYING TRACER OK PENDING INSPECTION OF (5) 4" HCS LATERALS WITH TRACER WIRE VERIFICATION OF GRADE, AIR TESTING OF PIPING, VACUUM TESTING OF MANHOLE, AUTHORIZATION TO DISCHARGE FROM ADEQ AT LATER DATE. |
|
| 04/18/2006 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR CANCELLED |
|
| 04/17/2006 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* PROVIDE LISTING OR APPROVED TRANSITION COUPLING FOR DUCTILE TO SDR 35 |
|
| 04/14/2006 | SITE - SEWER | Partial Approval | IVRS - Inspection :* APPROVED PLAN ON SITE 6" DUCTILE FROM MANHOLE #2 20' WEST TO EDGE OF ROAD WAY OK. PROVIDE LISTING FOR TRANSITION DOUBLE HUB OR PROVIDE APPROVED COUPLING FOR DUCTILE TO SDR 35 TRANSITION. 1. THIS SEWER WILL REQUIRE VERIFICATION OF GRADE, AIR TESTING ON PIPING, VACUUM TESTING ON MANHOLES AND AUTHORIZATION TO DISCHARGE FROM ADEQ FOR FINAL. |