Permit: T06PL00601

Parcel: 110121020


Addresses:

2715 N WYATT DR


Inspection Status: Not ready for Inspection

Inspection History: SITE - SEWER

Permit Number - T06PL00601

Inspection Description - SITE - SEWER

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
04/25/2006 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
04/25/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
FROM #3 TO MANHOLE #1 OK
AIR TEST FROM MANHOLE #3 TO MANHOLE #1 INCLUDING HCS LATERALS OK
04/20/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
INSTALLATION OF (5) 4" HCS LATERALS TO 2-WAY CLEANOUT OK
04/19/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
FROM EXISTING MANHOLE #3 WEST TO 20', 6" DUCTILE IRON TRANSITION TO 6" SDR 35 TO MANHOLE #1 (NEW) INCLUDING (5) 6X4 HCS WYES, SHADING, BEDDING, LAYING TRACER OK
PENDING INSPECTION OF (5) 4" HCS LATERALS WITH TRACER WIRE VERIFICATION OF GRADE, AIR TESTING OF PIPING, VACUUM TESTING OF MANHOLE, AUTHORIZATION TO DISCHARGE FROM ADEQ AT LATER DATE.
04/18/2006 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELLED
04/17/2006 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
PROVIDE LISTING OR APPROVED TRANSITION COUPLING FOR DUCTILE TO SDR 35
04/14/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
APPROVED PLAN ON SITE 6" DUCTILE FROM MANHOLE #2
20' WEST TO EDGE OF ROAD WAY OK.
PROVIDE LISTING FOR TRANSITION DOUBLE HUB OR PROVIDE APPROVED COUPLING FOR DUCTILE TO SDR 35 TRANSITION.
1. THIS SEWER WILL REQUIRE VERIFICATION OF GRADE, AIR TESTING ON PIPING, VACUUM TESTING ON MANHOLES AND AUTHORIZATION TO DISCHARGE FROM ADEQ FOR FINAL.