Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 06/23/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTES FROM PAST INSPECTION AND COMPLY. |
|
| 05/12/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* SEE NOTE #1 & #2 BRASS TEE IS REQUIRED AT COPPER MALE ADAPTOR. VACUUM BREAKER IS REQUIRED ON HOSE BIB. |
|
| 05/08/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE BRASS TEE AND VACUUM BREAKER AT HOSE BIBB. 2. PROVIDE NIPPLE WITH NO THREADS ON DISCHARGE END AT 125# PRESSURE RELIEF DEVICE. 3. T&P DRAIN LINE TO BE 1" ABOVE TOP OF PAN. 4. PROVIDE 3-GALV SCREWS AT EACH JOINT OF WATER HEATER VENT PIPING. PETITION OF APPEAL ON SITE #2006.04 |