Permit: T06PL00590

Parcel: 126062280


Addresses:

4002 E 4TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
07/12/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
06/01/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE DOUBLE WALL VENT PIPE FROM ENCLOSURE TO ABOVE ROOF WITH AN APPROVED CAP.
PROVIDE MIN. 3 SCREWS IN ALL JOINTS OF VENT CONNECTOR
SECURE VENT.
TERMINATE 125 PSI T&P VALVE DOWNLOAD WITH NO THREADS
BE SURE WATER HEATER VENT TERMINATES MIN. 2' ABOVE COMBUSTION AIR VENT.