Permit: T06PL00584

Parcel: 12612264A


Addresses:

4637 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06PL00584

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/21/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
04/13/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
PEX WATER PIPING IS OK,
BACKFILL WITH CLEAN FILL 3/4" MNVS
COPPER PIPING AT SERVICE IS REQUIRED TO BE TYPE L
BACKFLOW INSTALLATION REQUIRES A PERMIT FROM TUCSON WATER AND A CERTIFICATION TEST.
BACKFLOW INSTALLATION ALSO REQUIRES A UNION AT ASSEMBLY THAT WILL ALLOW REMOVAL OF ASSEMBLY.
RELIEF VALVE SHALL POINT DOWN AND HAVE 12" OF CLEARANCE.