Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
Permit Number - T06PL00552
Inspection Description - PLUMBING - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/14/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL GAS VALVES TO BE AGA OR CSA APPROVED SHUT OFF VALVES. 2. PVC SCH 40 PIPING IS NOT LISTED PIPING FOR GAS ANY LONGER. 3. PROVIDE LISTING FOR REPAIR COUPLINGS FROM PVC TO P.E. -- PROVIDE ACCESS INTO POOL HOUSE BUILDING FOR INSPECTION. 4. PROVIDE MINIMUM TEST THAT SHALL NO DROP FOR DURATION OF TEST PERIOD. 5. POOL HEATERS SHALL HAVE APPROVED PRESSURE RELIEF TERMINATED CORRECTLY. 6. SHALL HAVE ACCESS TO ENTIRE GAS SYSTEM. MAY NOT BE A COMPLETE LIST. |
|
| 04/12/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* TEST AT O - SEE NOTES FROM 4/6/06 INSPECTION. |
|
| 04/06/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLEASE POST AN ADDRESS 2. IF THIS IS THE 2" SERVING THE POOL AREA THIS REQUIRES APPROVED PIPING MATERIAL FOR NATURAL GAS WITH TEST AT TIME OF INSPECTION. AND ACCESS TO ENTIRE GAS SYSTEM FROM THIS METER. 3. HAVE A CONTACT PHONE NUMBER 4. GAS PIPING REQUIRES LICENSED PLUMBING CONTRACTOR. THIS IS NOT A COMPLETE LIST. |