Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/06/2006 | PLUMBING - GAS PRESSURE TEST | Approved | ||
| 04/03/2006 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* - PRESSURE TEST ON YARD PIPING OK - PIPING OK TO COVER - PROVIDE TEST ON M.H. - RAISE WH VENT TO ABOVE COOLER - PROVIDE COMBUSTION AIR OPENINGS AT WH - SUPPORT PIPING AT SERVICE - PROVIDE DIELECTRIC UNION AND A FLEX RATED FOR MOBILE HOME SERVICE. |