Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* OK FOR GAS |
|
| 04/03/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE FLASHING AT ROOF PENETRATION 2. PROVIDE DOUBLE WALL TYPE B FLUE VENT THRU CEILING/ROOF AND ABOVE ROOF. TERMINATE TYPE B VENT MIN. 1' ABOVE ROOF W/LISTED VENT CAP. 3. PROVIDE AN OPERATING T&P RELIEF VALVE AND TERMINATE OUTSIDE, 6" ABOVE GROUND W/APPROVED MATERIALS AND WITHOUT THREADS. 4. PROVIDE ELECTRICAL BONDING (GROUND BETWEEN GAS & WATER PIPING) 5. SEAL WALL PENETRATIONS PRESSURE DROPPING CHECK FOR LEAKS. REPRESSURE TEST RECALL FOR INSPECTION AFTER COMPLETING. |