Permit: T06PL00518

Parcel: 132090300


Addresses:

2909 E RICKEY VISTA

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/07/2006 PLUMBING - FINAL Approved OK FOR GAS
CALL 889-1888
03/31/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PRESSURE TEST IS OK
YARD PIPING IS OK TO COVER
1. PROVIDE COMBUSTION AIR OPENINGS FOR WATER HEATER.
2 OPENINGS, UPPER & LOWER MINIMUM 10X10 EA.
2. TEMPERATURE & PRESSURE RELIEF VALVE MUST TERMINATE OUTSIDE, VERTICALLY. USE APPROVED MATERIALS. COPPER OF CPVC OR OBTAIN VARIANCE.
3. PROVIDE BONDING OF GAS LINE.
RECALL FINAL INSPECTION.