Permit: T06PL00504

Parcel: 125111560


Addresses:

3701 E 3RD ST #10

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
05/24/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
LEFT GAS CARD
05/10/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
15 PSI TEST IS OK
OK TO BACKFILL TRENCH
PROVIDE PROPER SIZE T&P DRAIN TO DAYLIGHT SLOPE DOWNWARD
UNIT #11 PROVIDE T&P DRAIN TO DAYLIGHT, SLOPE DOWNWARD.
04/27/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
GAUGE READING 2 PSI
THERE IS A LEAK
USE SOAPY WATER TO CHECK FOR LEAKS.
04/06/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
UNITS 10 & 11 HOLDING PRESSURE. LEFT GAS CARDS.
RECALL FOR INSPECTION ON UNIT 12
04/04/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
UNIT 10 DO NOT USE A 100LB GAUGE.
UNIT 11 GAUGE DOES NOT WORK PROPERLY.
UNIT 12 NOT HOLDING PRESSURE.
ALL TEST GAUGES SHOULD BE 1/60TH LB INCREMENTS (15 PSI GAUGE)
EVERYTHING ELSE IS OK
03/29/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE AGA OR CSA APPROVED GAS SHUT OFF VALVES AT WATER HEATERS.
PROVIDE MIN 3 SCREWS IN VENT CONNECTORS.
PROVIDE A TEST ON ENTIRE GAS SYSTEMS.
MUST USE APPROVED TAPE PRIMER PRIOR TO TAPING JOINGS & TOOL MARKS.
VENT PIPE EXTENSIONS ON ROOF MUST BE DOUBLE WALL PIPE W/APPROVED CAPS.
03/27/2006 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
GATE LOCKED (BOTH) NO ACCESS