Permit: T06PL00499

Parcel: 127041640


Addresses:

4949 E 3RD ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/26/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
12 PSI TEST FROM METER UNDERGROUND UP AT BUILDING OVERHEAD PER APPROVED PLAN. GAS CARD AT METER.
04/25/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
04/07/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
10 PSI TEST FROM METER TO WATER HEATER, (2) WALL HEATERS AND 3/4" DROP TO ? TOTAL DEMAND IS UNKNOWN. NEED CITY APPROVED GAS ISOMETRIC OF GAS SYSTEM AS REQUESTED ON 3/27/06. SEE ITEMS #4 PROVIDE CLEAN AREA AT BONDING SITE. #6 ALL ITEMS TO BE ADDRESSED.
GAS PIPING CANNOT BE DIRECTLY EMBEDDED IN CONCRETE.
PLEASE HAVE RETEST AT TIME OF INSPECTION.
03/27/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE MINIMUM TEST ON GAS SYSTEM AND PROVIDE TEST GAUGE IN 1/10 POUND INCREMENTS.
2. WATER HEATER TEMPERATURE & PRESSURE RELIEF DRAIN PIPING SHALL BE FULL SIZE APPROVED PIPING GRAVITY DRAIN TO DAYLIGHT.
3. ALL APPLIANCES TO HAVE APPROVED CSA OR AGA GAS SHUT OFF VALVES.
4. PROVIDE BONDING OF BUILDING GAS PIPING.
5. WATER HEATER ENCLOSURE SHALL REQUIRE MINIMUM
100 SQ. INCHES UPPER & LOWER COMBUSTION AIR.
6. WATER HEATER FLUE VENT REQUIRES 3-GALV SCREWS AT EACH JOINT. DOUBLE WALL VENT THRU ROOF WITH APPROVED VENT CAP - MINIMUM 1" CLEARANCE FROM COMBUSTIBLES.
7. PROVIDE CITY APPROVED GAS ISOMETRIC OF SYSTEM WHEN ADDING GAS FIXTURES.