Permit: T06PL00495

Parcel: 137071620


Addresses:

142 W BORREGO ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
04/04/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
03/31/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
PROVIDE DOUBLE WALL B VENT AT EXTERIOR LOCATIONS
PROVIDE DOUBLE WALL B VENT CAP
SECURE VENT WITH SHEET METAL SCREWS.
CONNECT WATER TO WH IN ORDER TO CHECK T&P VALVE
SUPPORT 3/4 PIPING AT 90 DEGREES.
RECALL FOR FINAL INSPECTION AFTER COMPLETING.
OK FOR GAS CALL 889-1888
03/27/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ELIMINATE PIPING UNDER ROOM ADDITION.
RE-ROUTE PIPING TO EXISTING 3/4 PIPING AT EXISTING HOUSE CONNECTION.
2. INDOOR APPLIANCES INSTALLED OUTSIDE REQUIRE PROTECTION. INSTALL WH ENCLOSURE TO PROTECT WATER HEATER.
3. PROVIDE TYPE B VENT ON WATER HEATER, EXTEND TO ABOVE SWAMP COOLER. USE FLASHING WHERE PENETRATING EVE.
4. TERMINATE T&P DRAIN 6" ABOVE GROUND, USE APPROVED MATERIALS, NO THREADS ON END.
5. PROVIDE ELECTRICAL BONDING.
OK TO BURY YARD PIPING IF HOLDING TEST.