Permit: T06PL00456

Parcel: 126132960


Addresses:

4619 E MONTECITO ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06PL00456

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/20/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
15 PSI TEST PER APPROVED PLAN
GAS CARD AT METER
SW GAS 889-1888
10/16/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. HAVE NEW WATER HEATER ADDED TO THIS PERMIT.
2. PROVIDE CITY APPROVED GAS ISOMETRIC OF YOUR GAS SYSTEM SHOWING ALL CURRENT & FUTURE GAS USING APPLIANCES.
3. PROVIDE CORRECT VENT CAP FOR FUTURE WYE BRANCH CONNECTION AT WATER HEATER.
4. YOUR GAS PIPING MAY BE UNDERSIZED DEPENDING ON YOUR APPROVED PLAN.
5. RETEST SYSTEM AT REINSPECTION.
6. PRIME & TAPE ALL TOOL MARKS & FITTINGS ON UNDERGROUND PIPING.
08/22/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SHALL PROVIDE ROOF FLASHING AT PIPE PENETRATIONS THRU ROOF.
2. TEST SHALL BE IN PLACE WITH MINIMUM TEST PRESSURE WITH NO PRESSURE LOSS.
3. PROVIDE FACTORY COATED PIPING FOR ALL UNDERGROUND PIPING, PRIMED THEN TAPED TO PREVENT CORROSION.
4. PROVIDE CORRECT VENTING FOR WATER HEATER & FURNACE. FURNACE (LARGER VENT) SHALL BE LOWER CONNECTION, WITH APPROVED VENT FITTING, DOUBLE WALL THRU CEILING + ROOF TERMINATING MINIMUM 10' FROM COOLER INTAKE OR 2' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' WITH APPROVED DOUBLE WALL VENT PIPING & CAP
5. PROVIDE FULL SIZE WATER HEATER TEMPERATURE & PRESSURE RELIEF DRAIN GRAVITY DRAIN TO DAYLIGHT.
6. FURNACE TO HAVE AGA OR CSA APPROVED GAS SHUT OFF VALVE IN SERVICEABLE LOCATION WITHIN 3' OF FURNACE.
7. GAS PIPING SHALL BE MINIMUM 3" ABOVE FINISH GRADE.
8. PROVIDE BONDING OF BUILDING GAS PIPING.
NOT COMPLETE LIST.
08/14/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO ACCESS AT 11:51 SHALL PROVIDE ACCESS AT REINSPECTION.
NOTE: GAS PIPING SHALL NOT BE INSTALLED UNDERGROUND UNDER A BUILDING OR STRUCTURE UNLESS IT MEETS 2003 UPC REQUIREMENTS FOR SLEEVING & VENTING.