Permit: T06PL00439

Parcel: 130181420


Addresses:

2026 S MONTEZUMA AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/25/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
PET. OF APPEAL #2006 061-4/21/06
OK FOR GAS
03/31/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
REMOVE CONCEALED UNION
PRIMER WRAP ALL TOOL MARKS ON SCOTCH KOTE
PROVIDE SCOTCH KOTE IN ALL AREAS BELOW GRADE
PROVIDE ELECTRICAL BONDING
PROVIDE ROOF FLASHING AT EVE
SUPPORT PIPE ON ROOF W/WEATHER RESISTANT PIPE SUPPORTS AND APPROVED CLAMPS.
T&P MUST GRAVITY DRAIN TO EXTERIOR OR APPLY FOR A CODE VEARIANCE AT THE PERMIT COUNTER 201 N STONE
SECURE VENT ON FURNACE W/SHEET METAL SCREWS
PROVIDE CORRECT VENTING MATERIAL ON FURNACE
USE CORRECT FLEX AT STOVE FOR 65000 BTU RATING
APPROVED PLAN CALLS FOR 1 1/4" PIPING. I VERIFIED THIS AND 1 1/4" IS REQUIRED FOR 247000 BTU AT 90'
PROVIDE 1 1/4" PIPING TO FIRT TEE.