Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* PET. OF APPEAL #2006 061-4/21/06 OK FOR GAS |
|
| 03/31/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* REMOVE CONCEALED UNION PRIMER WRAP ALL TOOL MARKS ON SCOTCH KOTE PROVIDE SCOTCH KOTE IN ALL AREAS BELOW GRADE PROVIDE ELECTRICAL BONDING PROVIDE ROOF FLASHING AT EVE SUPPORT PIPE ON ROOF W/WEATHER RESISTANT PIPE SUPPORTS AND APPROVED CLAMPS. T&P MUST GRAVITY DRAIN TO EXTERIOR OR APPLY FOR A CODE VEARIANCE AT THE PERMIT COUNTER 201 N STONE SECURE VENT ON FURNACE W/SHEET METAL SCREWS PROVIDE CORRECT VENTING MATERIAL ON FURNACE USE CORRECT FLEX AT STOVE FOR 65000 BTU RATING APPROVED PLAN CALLS FOR 1 1/4" PIPING. I VERIFIED THIS AND 1 1/4" IS REQUIRED FOR 247000 BTU AT 90' PROVIDE 1 1/4" PIPING TO FIRT TEE. |