Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/17/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* CORRECTION MADE. THIS IS A GAS ON REPIPE NO GAS CLEARANCE CARD REQUIRED. CONTRACTOR TO TIE IN AT METER & APPLIANCES AND BE SURE OF NO LEAKAGE OF GAS AT THAT TIME. |
|
| 03/15/2006 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* IT IS NOT POSSIBLE TO ENSURE LINE TIGHTNESS IN A REASONABLE AMOUNT OF TIME WITH A 60 PSI GAUGE THAT HAS 2 PSI INCREMENTATION. PROVIDE A TEST GAUGE WITH 1/10 PSI INCREMENTATION CONNECT YARD PIPING TO HOUSE, TEST ENTIRE SYSTEM. SECURE UNISTRUT TO WALL REMOVE SHARP EDGES FROM UNISTART WHERE A SAFETY HAZARD MAY EXIST. SEAL WALL PENETRATION PROVIDE ELECTRICAL BONDING OK TO COVER YARD PIPING IF IT IS HOLDING PRESSURE TEST PIPING IN HOUSE IS OK OK TO COVER IF PRESSURE TEST IS HOLDING. |