Permit: T06PL00387

Parcel: 119044560


Addresses:

3560 S 7TH AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/10/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
03/09/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
OK FOR GAS
1. PROVIDE DOUBLE WALL B VENT ABOVE ROOF
YOU CANNOT TRANSITION FROM DOUBLE WALL TO SINGLE WALL, YOU CANNOT HAVE SINGLE WALL EXPOSED.
RECALL FOR FINAL INSPECTION -- 03090
03/07/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE A FLASHING AT ROOF PENETRATION
2. PROVIDE WEATHER RESISTANT BLOCKS TO SUPPORT PIPING ON ROOF.
3. EXTEND DOUBLE WALL B VENT UP THROUGH ROOF AND ABOVE PARAPET.
4. PROVIDE ELECTRICAL BONDING OF GAS LINE
5. TERMINATE T&P RELIEF DRAIN OUTSIDE 6" ABOVE GROUND WITHOUT THREADS, USE APPROVED MATERIALS.
6. SEAL WALL PENETRATIONS
7. SUPPORT HORIZONTAL PIPING ON WALL
RETEST, RECALL FOR INSPECTION.