Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06PL00377
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/14/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 10 PSI TEST IS OK LEFT GAS CARD CORRECTIONS HAVE BEEN MADE |
|
| 03/13/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE MINIMUM TEST AT TIME OF INSPECTION WITH TEST GAUGE THAT IS IN 1/1OTH POUND INCREMENTS. 2. PLASTIC GAS PIPING REQUIRES 18" MINIMUM COVER 3. PROVIDE AGA OR CSA APPROVED GAS VALVES AT ALL APPLIANCES AND AT SERVICE LOCATION IF VALUE IS DESIRED. 4. PROVIDE WEATHER SEAL AT ROOF FLASHINGS & MASTIC BLOCKING ON ROOF. 5. PROVIDE GOOD BOND ON COLD BONDING CLAMP (CLEAN OFF PAINT) 6. PROVIDE PERM CAPS ON OLD GAS PIPING 7. PROVIDE 3-GALV SCREWS AT EACH JOINT OF WATER HEATER/FURNACE FLUE VENT PIPE. REMOVE TAPE AT SINGLE TO DOUBLE WALL CONNECTION ON WATER HEATER FLUE VENT. 8. PROVIDE WORKING TEMPERATURE & PRESSURE RELIEF FOR WATER HEATER 9. VENTS WITHIN 10' OF COOLER INTAKE TO BE 3' ABOVE FOR WATER HEATER AND 2' ABOVE FOR FURNACE WHEN WITHIN 10' |