Permit: T06PL00326

Parcel: 13308001D

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/24/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
14 PSI TEST FROM METER P.E. UNDERGROUND UP AT BUILDING OVERHEAD TO FURNACE/WATER HEATER OK
GAS CARD AT METER - SW GAS 889-1888
02/23/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLASTIC PIPING FOR GAS REQUIRES 18" MINIMUM COVER WITH GOOD MATERIAL AS BEDDING AND BACKFILL.
2. PROVIDE TEST GAUGE WITH 1/10 POUND INCREMENTS WITH MINIMUM TEST PRESSURE WITH NO LOSS FOR MINIMUM TIME
3. PROVIDE PLUG IN WATER HEATER PAN
4. PROVIDE NIPPLE IN 125# PRESSURE RELIEF WITH NO THREADED END
5. BONDING WIRE IS TO BE CONNECTE TO BUILDING COLD PIPE NOT FLEX.
PETITION OF APPEAL IS ON SITE