Permit: T06PL00309

Parcel: 138200130


Addresses:

6950 S LUNDY DR

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
03/29/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
02/28/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
PVC FEMALE THREADS NOT ALLOWED WITH METAL MALE THREADS
EXCPOSED PVC IS LIMITED TO 24" VERTICAL ABOVE GROUND AND MUST BE WRAPPED WITH 40 MIL TAPE.
HB REQUIRE VACUUM BREAKERS
BLUE TRACER WIRE REQUIRED ON ALL UNDERGROUND WATER PIPING -- ATTACH TO PIPING AT 8'