Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06PL00305
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/13/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1. CORRECTIONS MADE OK 2. GAS IS ON 3. PLUMBING FINAL OK |
|
| 02/24/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*REQUIRE TO RUN 2" ALL THE WAY TO THE METER REDUCED TO 3/4" AT PIZZA OVEN AND CONNECTED TO A 1" FLEX CONNECTOR NOT INSTALLED PER PLAN. GAS TO WATER HEATER NOT ON THE PLAN. PLUMBERS TAPE NOT APPROVED STRAP DOES WATER HEATER HAVE EXPANSION TANK? S.W GAS WILL NOT CHANGE OUT THE UNDERSIZED METER UNTIL THEY HAVE THE CLEARANCE CARD: WAS LEFT |
|
| 02/23/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. THE GAS METER MARKED 605 N 4TH AV IS ON 2. WILL REQUIRE GAS ISOMETRIC WITH DEVELOPED LENGTH AND TOTAL BTU CONSUMPTION. 3. PROVIDE NAME AND LICENSE OF PLUMBER 4. NO BOND BETWEEN GAS AND WATER NO FLASHING THRU ROOF PLAN ON SITE NO ACCESS TO ROOF 5. I AM UNABLE TO FINAL THIS INSPECTION UNTIL ALL PIPING IS COMPLETE AND HOOKED UP. THERE IS NO METER AT THIS TIME. |