Permit: T06PL00303

Parcel: 129131750


Addresses:

932 E 32ND ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
02/27/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
1) OK FOR GAS CALL S.W. GAS
02/22/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
UNIT #2
1. PROVIDE PROTECTION FOR WATER HEATER INSTALLED OUTDOORS
2. PROVIDE A OPERATION T&P RELIEF DRAIN AND TERMINATE VERTICALLY
3. PROVIDE LISTED PIPING AND VENT SUPPORTS, METAL TAPING IS NOT AN APPROVED HANGER
4. PROVIDE LEVEL BASE FOR WH TO REST ON
5. PROVIDE ELECTRICAL BONDING OF GAS LINE
6. PROVIDE A PRESSURE TEST W/A GAUGE THAT HAS 1/10 PSI INCREMENTATION IN ORDER TO ACCURATELY DETERMINE LINE TIGHTNESS IN A REASONABLE PERIOD OF TIME.