Permit: T06PL00301

Parcel: 14043011A


Addresses:

6900 S PARK AV


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06PL00301

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/24/2008 PLUMBING - FINAL Approved REFERENCE T06PL00667
02/17/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PRESSURE GAUGE ON 0
THERE APPEARS TO BE A LOW PRESSURE SYSTEM AND A MEDIUM PRESSURE SYSTEM BOTH SUPPLIED BY THE SAME MAIN GAS METER WHICH IS LOCKED OUT. THE REGULATOR AT THE LOW PRESSURE SYSTEM HAS BEEN REMOVED.
THE ENTIRE GAS SYSTEM WILL HAVE TO BE ADDRESSED.
THERE ARE REGULATORS AT INDOOR SUSPENDED HEATERS THAT ARE NOT VENTED TO THE OUTDOORS. THERE ARE SECTIONS OF PIPING THAT ARE NOT ADEQUATELY SUPPORTED
AN APPROVED PLAN WILL NEED TO BE SUBMITTED IN ORDER TO PROPERLY ASSESS THIS SYSTEM.
THREAD PROTECTORS USED AS COUPLINGS WON'T BE AN ISSUE PROVIDED THAT YOU CAN GET A PRESSURE TEST TO HOLD. THE VOLUME OF THIS SYSTEM WILL REQUIRE A 24 HR TEST.