Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06PL00301
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/24/2008 | PLUMBING - FINAL | Approved | REFERENCE T06PL00667 | |
02/17/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PRESSURE GAUGE ON 0 THERE APPEARS TO BE A LOW PRESSURE SYSTEM AND A MEDIUM PRESSURE SYSTEM BOTH SUPPLIED BY THE SAME MAIN GAS METER WHICH IS LOCKED OUT. THE REGULATOR AT THE LOW PRESSURE SYSTEM HAS BEEN REMOVED. THE ENTIRE GAS SYSTEM WILL HAVE TO BE ADDRESSED. THERE ARE REGULATORS AT INDOOR SUSPENDED HEATERS THAT ARE NOT VENTED TO THE OUTDOORS. THERE ARE SECTIONS OF PIPING THAT ARE NOT ADEQUATELY SUPPORTED AN APPROVED PLAN WILL NEED TO BE SUBMITTED IN ORDER TO PROPERLY ASSESS THIS SYSTEM. THREAD PROTECTORS USED AS COUPLINGS WON'T BE AN ISSUE PROVIDED THAT YOU CAN GET A PRESSURE TEST TO HOLD. THE VOLUME OF THIS SYSTEM WILL REQUIRE A 24 HR TEST. |