Permit: T06PL00290

Parcel: 136087950


Addresses:

9510 E 22ND ST

Inspection Status: Partial Approval

Inspection History: SITE - SEWER

Date Description Inspector Results Comments
08/08/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
6" HCS FROM MANHOLE #3 TO CLEANOUT
AIRTEST OK
WAITING ON AUTHORIZATION TO DISCHARGE FROM P.C.D.E.Q
08/04/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
4" FROM MANHOLE #6 TO CLEANOUT K AIR TEST OK
4" FROM MANHOLE #1 TO CLEANOUT B AIR TEST OK
4" FROM EXISTING MANHOLE 6722.02 TO CLEANOUT C AIR TEST OK
07/21/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
EXISTING MANHOLE 6722-02 TO MANHOLE #1 AIRTEST OK
RETEST OF MANHOLE #2 TO #3 AIR TEST OK
MANHOLE #4 TO CLEANOUT F AIR TEST OK
07/14/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
RETEST VACUUM TEST MANHOLE #6 OK
RETEST VACUUM TEST MANHOLE #4 OK
VACUUM TEST MANHOLE #2 OK

PRESSURE TEST 8" SDR FROM MANHOLE #5 TO #6 OK
PRESSURE TEST 8" SDR FROM MANHOLE #4 TO #5 OK
1. NEED TEST ON 6" OUT OF MANHOLE #4
PRESSURE TEST 8" SDR FROM MANHOLE #3 TO #4 OK
1. NEED TEST ON 6" OUT OF MANHOLE #3
PRESSURE TEST ON 8" SDR FROM MANHOLE #2 TO #3
NOT READY.
06/29/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
1) MANHOLE #1 VACUUM TEST-OK
2) MANHOLE #6 VACUUM TEST-DENIED
3) MANHOLE #5 VACUUM TEST-OK
4) MANHOLE #4 VACUUM TEST-DENIED
5) REINSPECTION OF DENIED TESTS REQUIRED
04/12/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
4" FROM MANHOLE #6722.02 THRU CLEANOUT C FOR FUTURE BEDDING, SHADING, TRACER OK
1. PROVIDE PERM CAP OR LONG RADIUS FITTING AT END OF LINE ON THIS 4".
04/11/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
4" HCS LATERAL TO CLEANOUT D,
4" HCS LATERAL TO CLEANOUT G
4" HCS LATERAL TO CLEANOUT H
4" HCS DIP LATERAL TO CLEANOUT I
4" HCS LATERAL DIP TO CLEANOUT J
BEDDING, SHADING, LAYING TRACERS OK
04/07/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
8" SDR CONTINUOUS TO MANHOLE #6 4" HCS LATERAL FROM MANHOLE #6 TO CLEANOUT K.
6" DIP FROM MANHOLE #3 TO CLEANOUT F
6" DIP FROM MANHOLE #4 TO CLEANOUT E
BEDDING, SHADING, LAYING OK
MANHOLE BASE #1, 2, 3 OK
04/04/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
8" SDR 35 CONTINUES EAST FROM MANHOLE #5 TO APP. 30' WEST OF MANHOLE #6 INCLUDING HCS WYE AT STATION 1639.45 4" BEDDING, SHADING, LAYING OK
03/30/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
8" SDR 35 CONTINUES EAST TO MANHOLE #3 THRU TO THE CONTINUES THRU TO MANHOLE #5 INCLUDING (2) HCS WYES FOR STA 1505.30 AND 1534.76 BEDDING, SHADING, LAYING OK
03/29/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
8" SDR FROM PUBLIC MANHOLE #2 AREA EAST TO PRIVATE MANHOLE #3 INCLUDING WYE BRANCH AT STATION 10-46.30 BEDDING, SHADOWS, LAYING OK
03/27/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
EXISTING MANHOLE 6722-02 TO MANHOLE #1
8" SDR 35 OK
1. WILL NEED PRESSURE AIR TEST ON PIPING, VACUUM TEST ON MANHOLES, VERIFICATION OF GRADE AT LATER DATE.
4" SDR 35 FROM MANHOLE 1 TO NORTH, TO STUB UP AT PAD 1 SAME NOTES.
03/24/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
500' SEWER ALREADY RAN AND BEING COVERED.
03/23/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
BEDDING IN PLACE FOR PIPING, RICK ENGINEERING TO BE ADEQ INSPECTOR.
OK TO START PIPE INSTALL.